Under Excitation Limiter: UEL2
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < Tuv < 0.5*Mult*TimeStep then Tuv = 0, ElseIf 0.5*Mult*TimeStep < Tuv < Mult*TimeStep then Tuv = Mult*TimeStep
- If 0.0 < Tup < 0.5*Mult*TimeStep then Tup = 0, ElseIf 0.5*Mult*TimeStep < Tup < Mult*TimeStep then Tup = Mult*TimeStep
- If 0.0 < Tuq < 0.5*Mult*TimeStep then Tuq = 0, ElseIf 0.5*Mult*TimeStep < Tuq < Mult*TimeStep then Tuq = Mult*TimeStep
- If 0.0 < TuL < 0.5*Mult*TimeStep then TuL = 0, ElseIf 0.5*Mult*TimeStep < TuL < Mult*TimeStep then TuL = Mult*TimeStep
- If 0.0 < Tu2 < 0.5*Mult*TimeStep then Tu2 = 0, ElseIf 0.5*Mult*TimeStep < Tu2 < Mult*TimeStep then Tu2 = Mult*TimeStep
- If 0.0 < Tu4 < 0.5*Mult*TimeStep then Tu4 = 0, ElseIf 0.5*Mult*TimeStep < Tu4 < Mult*TimeStep then Tu4 = Mult*TimeStep
- Kul and Kui: Kul can't be 0 if Kui = 0, if true then Kul changed to 40.
-
If VUImax < VUImin then swap the values. If VUImax < 0 then VUImax change sign to positive. If VUImin > 0 then change sign to negative.
- If VULmax < VULmin then swap the values. If VULmax < 0 then VULmax change sign to positive. If VULmin > 0 then change sign to negative.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters for UEL2 and UEL2_PTI:
| K1 | Voltage exponent |
| K2 | Voltage exponent |
| Qquad | 0: Mirror image around MVAR axix |
| Tuv | Voltage filter time constant, sec. |
| Tup | Real power filter time constant, sec. |
| Tuq | Reactive power filter time constant, sec. |
| Kui | Integral gain, p.u./sec |
| Kul | Proportional gain, p.u. |
| Vuimax | PI control block maximum output, p.u. |
| Vuimin | PI control block minimum output, p.u. |
| Kuf | Excitation system stabilizer gain, p.u. |
| Kfb | Gain |
| TuL | Time constant, sec. |
| Tu1 | Lead time constant, sec. |
| Tu2 | Lag time constant, sec. |
| Tu3 | Lead time constant, sec. |
| Tu4 | Lag time constant, sec. |
| P0 | Point 0 real power, p.u. |
| Q0 | Point 0 reactive power, p.u. |
| P1 | Point 1 real power, p.u. |
| Q1 | Point 1 reactive power, p.u. |
| P2 | Point 2 real power, p.u. |
| Q2 | Point 2 reactive power, p.u. |
| P3 | Point 3 real power, p.u. |
| Q3 | Point 3 reactive power, p.u. |
| P4 | Point 4 real power, p.u. |
| Q4 | Point 4 reactive power, p.u. |
| P5 | Point 5 real power, p.u. |
| Q5 | Point 5 reactive power, p.u. |
| P6 | Point 6 real power, p.u. |
| Q6 | Point 6 reactive power, p.u. |
| P7 | Point 7 real power, p.u. |
| Q7 | Point 7 reactive power, p.u. |
| P8 | Point 8 real power, p.u. |
| Q8 | Point 8 reactive power, p.u. |
| P9 | Point 9 real power, p.u. |
| Q9 | Point 9 reactive power, p.u. |
| P10 | Point 10 real power, p.u. |
| Q10 | Point 10 reactive power, p.u. |
| VULmax | Maximum limit, p.u. |
| VULmin | Minimum limit, p.u. |